11No Ignition

The heater tried to light the burner but no flame was detected, so it stopped. This is the most common Rinnai code and usually points to gas supply, venting or the igniter and flame rod.

Difficulty
Technician
Safety
Call a pro
Source
Confirmed by manufacturer
Last checked
2026-11-21
Safety: Involves gas, venting, refrigerant or electrical parts. Do the basic checks only, then call a licensed technician.

How to fix Rinnai code 11

  1. Make sure every gas valve feeding the heater (at the heater and at the meter) is fully open
  2. On propane, check that the tank isn't empty
  3. Check the outside vent terminal for snow, leaves, nests or anything blocking it
  4. Reset: turn off hot water taps and press ON/OFF on the controller twice
  5. If the code comes back, call a licensed Rinnai service provider

What 11 means on your Rinnai

Rinnai's first checks for code 11 are simple: every gas valve open, propane in the tank, and air purged from the gas lines. A recently refilled propane tank or new gas work is a common trigger.

If gas is fine, the cause is usually inside the heater: carbon or white deposits on the flame rod, a loose ("floating") flame rod or igniter, or a weak spark.

What a technician will check: inlet gas pressure with every gas appliance on high fire, gas type and gas settings, the spark and spark gap (3.5 mm), cleaning the flame rod and igniter (with a new gasket), the vent system and equivalent length, and the high-altitude setting.

If you smell gas, don't reset the heater. Leave the building and call your gas supplier.

Likely causes

  • Gas valve closed or propane tank empty
  • Air in the gas line after installation or tank refill
  • Low gas pressure or undersized gas line
  • Dirty or loose flame rod or igniter
  • Venting problem or wrong altitude setting