How to fix Carrier code 34
- Make sure the manual gas shut-off valve to the furnace is on
- Reset: switch the furnace power off for a few seconds and back on
- Have a technician clean the flame sensor and check gas pressure and the igniter
- If the code returns, call a licensed HVAC technician
What 34 means on your Carrier
Code 34 is Carrier's most searched code. The label's checklist starts with oxide build-up on the flame sensor, which Carrier says to clean with fine steel wool, and a flame signal of at least 5 microamps DC (4.0–6.0 nominal).
Other checks: gas valve defective or turned off, manual shut-off closed, control ground continuity, low inlet gas pressure, poor flame carryover, and a defective hot surface igniter. The green/yellow ground wire must be connected to the furnace sheet metal and the flame sensor must not be grounded.
Count the flashes: the first digit is the number of short flashes, the second the number of long flashes.
Likely causes
- Oxide build-up on the flame sensor
- Gas valve or manual shut-off off
- Low inlet gas pressure
- Defective hot surface igniter
- Poor control ground or grounded flame sensor
Parts and supplies for this fix
- Carrier flame sensorCheck price
- Carrier hot surface igniterCheck price
We may earn a commission from purchases made through these links. Confirm the part matches your exact model number before buying.