Safety: Turn the power off before any checks inside the unit.
How to fix Rheem code 90
- Remove any blockage from the air intake and vent exhaust (the air intake needs 12 in. / 30 cm of clearance)
- Reset: turn off hot faucets, power the heater off at the remote, wait about 5 minutes and turn it back on
- If the code is still shown, note it and call a qualified service technician
What 90 means on your Rheem
Rheem's chart groups codes 90 and 99: the air intake or vent exhaust opening may be blocked (remove the blockage; the air intake requires 12 in. / 30 cm of clearance), or the vent pipes at the termination may not be connected properly (contact a dealer or technician).
Vent pipes carry exhaust gases outside. If they look disconnected, turn the heater off and call for service.
Likely causes
- Blocked air intake or exhaust opening
- Vent pipes not connected properly at the termination